ENA400 (PQA)

ENA400 power quality analyzer is based on an industrial PC in a 19" case and up to 2 external signal conditioning kits (ENA-SCM-01A). One ENA-SCM-01A kit provides signal conditioning for up to 16 analog signals and optional digital inputs (up to 64). Digital inputs are sampled synchronously with analog inputs. The total number of voltage and current signals can go up to 32 (e.g. 5 x 3U+3I).

ENA400 is the best solution for customers, who are looking for a permanently installed Power Quality analyzer to monitor multiple 3-phases power systems. ENA-Node firmware module fault recorder and transient recorder can trigger and store analog quantities, together, with digital data.

ENA400 analyzer fully complies with the IEC 61000-4-30 standard, class A.

Specification

Technical Specification:

General
Storage intervals k*0.2 s/ 3 s/ k*1 min/ 10 min/ 15 min/ 2 h
Operating temperature 0 up to +50 °C
Storage temperature -30 up to +80 °C
Size 180 x 440 x 460 mm (h x w x d)
Weight 17 kg
Voltage Inputs
Number of inputs selectable 1x4, 2x4, 3x4, 4x3
Input ranges 60 V, 120 V (RMS) via ENA-SCM-01A module
Bandwidth 45 Hz to 2.5 kHz
Overvoltage protection 1 kV cont.
Input resistance 250 kOhm, 10 pF
Isolation voltage 4.2 kV RMS, 50 Hz, 1 min
Accuracy +/-0,1 %
Connection 1-phase, 3-phase, 3-phase + N, star, delta and Aron
Current Inputs
Number of inputs selectable 1x4, 2x4, 3x4, 4x3
Input ranges 1 A, 5 A via ENA-SCM-01A module or
according to used current clamps
Accuracy +/-0,1 %
Standards
Safety IEC 60950
EMC IEC 61000-6-2, IEC 61000-4-2 to 6
Power Quality Analysis EN 50160, IEC 61000-4-7,
IEC 61000-4-15, IEC 61000-4-30
Hardware
Memory 512 MB RAM
Processor Intel® Pentium® 4 (2 GHz)
HDD 40 GB
Display Optional, can be connected via VGA output
Interface VGA, USB, 2x RS232, 2x Ethernet
A/D converter 16 bits
Sampling frequency 9600S/s, 19200S/s, 38400S/s
Power supply 180 ol 265 V AC, 47 to 63 Hz or optional 24 V DC
Power consumption 120 VA

Download