ENA510-PMU

Model ENA510 is built in a rugged plastic PELI case. The analyzer has a durable construction useful for field measurements. It allows monitoring of one or two three-phase voltage and current systems. Currents are measured using current clamps. The analyzer can be controlled via a built-in touch screen with surface hardness 7H (diamond has 10H). Access to the analyzer can be done remotely using Ethernet or Wi-Fi too.

The analyzer is equipped with a remote GPS signal receiver for precise time synchronization and phasor measurement according IEEE C37.118.
Additionally the analyzer has 16 digital inputs (24 V).

Available models of ENA510:

  • 1x 4U + 1x 4I
  • 1x 4U + 3x 4I
  • 2x 4U + 2x 4I
  • 4x 4U

Specification

Technical specification:

General
Storage intervals k*1 min/ 10 min/ 15 min/ 2 h
Operating temperature -10 to +50 °C
Storage temperature -40 to +85 °C
Size 170 x 480 x 360 mm (h x w x d)
Weight 8 kg
Voltage inputs
Number of inputs 4 or 8
Input ranges 75 V, 150 V, 300 V, 600 V
Bandwidth 45 Hz to 3 kHz
Isolation 4,2 kV RMS, 50 Hz, 5 s, Ch-Ch, Ch-GND
Accuracy +/-0,1 %
Connection 1-phase, 3-phase, star, delta and Aron
Current inputs
Number of inputs 4, 8 or 12
Input ranges According to used current clamps (for example MN71 2 A, 10 A or AMPFLEX 30 A, 300 A, 3000 A)
Bandwidth 45 Hz to 3 kHz
Isolation According to clamps
Accuracy +/-0,1 %
Digital inputs/outputs
Number of inputs 16 DI, 24 V DC
Standards
Safety EN 61010-1:2004
EMC IEC 61000-6-2, IEC 61000-4-2 až 6
Analysis procedure EN 50160, EN 61000-4-7, EN 61000-4-15, EN 61000-4-30
Hardware
Memory 128 MB RAM sbRIO + 1 GB PC
Processor PowerPC 400 MHz + Intel ATOM
Storage 150 GB HDD
Display Touch display
Operating system VxWorks + WinXPemb
Interface Ethernet
A/D converter 16 bits
Sampling frequency 9600S/s adaptiv
Power supply 180 up to 265 V AC, 47-63 Hz
Power consumption Max 60 VA