Elcom Network Analyzer model ENA300

Characteristics:

Elcom Network Analyzer ENA300The ENA300 Power Quality Analyzer is primarily designed as a cost effective solution for school and university labs. The ENA300 provides programmable signal conditioning (4 voltage and 4 current input channels) and embedded 16-bit A/D converter with a USB interface. The ENA300 has no CPU and therefore must be connected to an external PC via USB interface. The external PC runs the actual ENA300 instrument firmware on Windows XP operating system.

The ENA300 uses the same firmware and provides the same measurement functionality and precision as the rest of ENA series instruments.

ENA300 analyzer fully complies with the IEC 61000-4-30 standard, class A.

 

Technical Specification:

General
Storage intervalsk*0.2s/ 3s/ k*1min/ 10min/ 15min/ 2h
Operating temperature-25 up to +50°C
Storage temperature-30 up to +80°C
Size66 x 308 x 257mm (h x w x d)
Weight1.2kg
Voltage Inputs
Number of inputs4
Input ranges450V, 250V, 110V, 65V (RMS)
Bandwidth45Hz up to 2.5kHz
Input resistance200kOhm, 10pF
Isolation voltage4.2kV RMS, 50Hz, 1min
Accuracy+/-0.1%
Connection1-phase, 3-phase, 3-phase + N, star, delta and Aron
Current Inputs
Number of inputs4
Input rangesaccording to used current clamps
Bandwidth45Hz up to 2.5kHz
Accuracy+/-0.1%
Standards
SafetyIEC 60950
EMCIEC 61000-6-2, IEC 61000-4-2 to 6
Power Quality AnalysisEN 50160, IEC 61000-4-7,
IEC 61000-4-15, IEC 61000-4-30
Hardware
Communication interfaceUSB
A/D converter16 bits
Sampling frequency9600S/s, 19200S/s, 38400S/s
Power supply180 to 265V AC, 47 to 63Hz
Power consumption10VA

Download: