Elcom Network Analyzer ENA460Power quality analyzer ENA460 is based on NI sbRIO (PowerPC processor + FPGA) and signal conditioning for 4 voltages and 4 currents. ENA460 compact aluminium case mounts directly on a 35mm DIN rail.

Key features:

  • 4 galvanic isolated voltage inputs with antialiasing filters
  • 4 galvanic isolated direct current inputs with antialiasing filters
  • Adaptive sampling frequency
  • Dimensions: 170 x 230 x 120mm (H x W x D)
  • A/D converter with 16-bit resolution
  • Optional galvanic isolated digital inputs and outputs
  • Consumes less than 20VA
  • No rotating parts for high reliability
  • Operating system VxWorks 

ENA460 analyzer fully complies with the IEC 61000-4-30 standard, class A.

 

Technical specification:

Generally
Storage intervalsk*1min/ 10min/ 15min/ 2h
Operating temperature-20 up to +55°C
Storage temperature-40 up to +85°C
Size170 x 230 x 120mm (h x w x d)
Weight3.5kg
Voltage inputs
Number of inputs4
Input ranges57.7V, 100V RMS (measurable up to 2xUn)
Bandwidth45Hz up to 3kHz
Isolation4200V (50Hz / 5s), Ch-Ch, Ch-GND
Accuracy+/-0.1%
Connection1-phase, 3-phase, star, delta and Aron
Current inputs
Number of inputs4
Input ranges1A, 5A RMS (measurable up to 2xUn)
Bandwidth

45Hz up to 3kHz

Isolation4200V (50Hz / 5s), Ch-Ch, Ch-GND
Accuracy+/-0,1%
Digital inputs/outputs
Number of inputs4 DI + 4 DO, galvanic isolated
Standards
SafetyIEC 60950
EMCIEC 61000-6-2, IEC 61000-4-2 to 6
Analysis procedureEN 50160, IEC 61000-4-7, IEC 61000-4-15, IEC 61000-4-30
Hardware
Memory128MB RAM
ProcessorPowerPC 400MHz
Storage265MB internal or 1GB-16GB CF
Operating systemVxWorks
InterfaceEthernet
A/D converter16 bits
Sampling frequency9600S/s adaptive
Power supply180 up to 265V AC, 47-63Hz
Power consumptionmax 20VA