Elcom Network Analyzer model ENA510
Characteristic:

Model ENA510 is built in a rugged plastic PELI case. Analyzer has durable construction useful for field measurements. It allows monitoring one or two three-phase voltage and current systems, currents are measured using current clamps.
Analyzer can be controlled via built-in touch screen with surface hardness 7H (diamond has 10H). Access to the analyzer can be done remotely using Ethernet or Wi-Fi too.
Analyzer is equipped with remote GPS signal receiver for precise time synchronization and phasors measurement according IEEE C37.118.
Additionally analyzer has 16 digital inputs (24V).
Available models of ENA510: - 1x 4U + 1x 4I
- 1x 4U + 3x 4I
- 2x 4U + 2x 4I
- 4x 4U
Technical specification:
Generally
| Storage intervals | k*1min/ 10min/ 15min/ 2h |
| Operating temperature | -10 to +50°C |
| Storage temperature | -40 to +85°C |
| Size | 170 x 480 x 360 mm (h x w x d) |
| Weight | 8kg |
Voltage inputs
| Number of inputs | 4 or 8 |
| Input ranges | 75, 150V, 300V, 600V |
| Bandwidth | 45Hz to 3kHz |
| Isolation | 4,2kV RMS, 50Hz, 5s, Ch-Ch, Ch-GND |
| Accuracy | +/-0,1% |
| Connection | 1-phase, 3-phase, star, delta and Aron |
Current inputs
| Number of inputs | 4, 8 or 12 |
| Input ranges | according to used current clamps (for example MN71 2A, 10A or AMPFLEX 30A, 300A, 3000A) |
| Bandwidth | 45Hz to 3kHz |
| Isolation | according to clamps |
| Accuracy | +/-0,1% |
Digital inputs/outputs
| Number of inputs | 16 DI, 24V DC |
Standards
| Safety | EN 61010-1:2004 |
| EMC | IEC 61000-6-2, IEC 61000-4-2 až 6 |
| Analysis procedure | EN 50160, EN 61000-4-7, EN 61000-4-15, EN 61000-4-30 |
Hardware
| Memory | 128MB RAM sbRIO + 1GB PC |
| Processor | PowerPC 400MHz + Intel ATOM |
| Storage | 150GB HDD |
| Display | touch display |
| Operating system | VxWorks + WinXPemb |
| Interface | Ethernet |
| A/D converter | 16 bits |
| Sampling frequency | 9600S/s adaptiv |
| Power supply | 180 up to 265V AC, 47-63Hz |
| Power consumption | max 60VA |