Elcom Network Analyzer model ENA510

Characteristic:

ENA510

Model ENA510 is built in a rugged plastic PELI case. Analyzer has durable construction useful for field measurements. It allows monitoring one or two three-phase voltage and current systems, currents are measured using current clamps.
Analyzer can be controlled via built-in touch screen with surface hardness 7H (diamond has 10H). Access to the analyzer can be done remotely using Ethernet or Wi-Fi too.

Analyzer is equipped with remote GPS signal receiver for precise time synchronization and phasors measurement according IEEE C37.118.
Additionally analyzer has 16 digital inputs (24V).

Available models of ENA510:
  • 1x 4U + 1x 4I
  • 1x 4U + 3x 4I
  • 2x 4U + 2x 4I
  • 4x 4U

Technical specification:

Generally
Storage intervalsk*1min/ 10min/ 15min/ 2h
Operating temperature-10 to +50°C
Storage temperature-40 to +85°C
Size170 x 480 x 360 mm (h x w x d)
Weight8kg
Voltage inputs
Number of inputs4 or 8
Input ranges75, 150V, 300V, 600V
Bandwidth45Hz to 3kHz
Isolation4,2kV RMS, 50Hz, 5s, Ch-Ch, Ch-GND
Accuracy+/-0,1%
Connection1-phase, 3-phase, star, delta and Aron
Current inputs
Number of inputs4, 8 or 12
Input ranges

according to used current clamps (for example MN71 2A, 10A or AMPFLEX 30A, 300A, 3000A)

Bandwidth45Hz to 3kHz
Isolationaccording to clamps
Accuracy+/-0,1%
Digital inputs/outputs
Number of inputs16 DI, 24V DC
Standards
SafetyEN 61010-1:2004
EMCIEC 61000-6-2, IEC 61000-4-2 až 6
Analysis procedureEN 50160, EN 61000-4-7, EN 61000-4-15, EN 61000-4-30
Hardware
Memory128MB RAM sbRIO + 1GB PC
ProcessorPowerPC 400MHz + Intel ATOM
Storage150GB HDD
Displaytouch display
Operating systemVxWorks + WinXPemb
InterfaceEthernet
A/D converter16 bits
Sampling frequency9600S/s adaptiv
Power supply180 up to 265V AC, 47-63Hz
Power consumptionmax 60VA

Download:



Top



[ Homepage ] [ Česky ]


ELCOM, a.s. | ELCOM, a.s. - Contacts

© 2013 ELCOM, a.s.